478 kW Perkins generator: 8.5 % less NOx on the same diesel, just cleaned

Can cleaner diesel alone lower emissions? Optimum Power Services measured the exhaust of a Perkins generator at full load before and after filtering the same stored diesel. NOx fell from 684.9 to 628.0 ppm, 8.5 %, and there was visibly less smoke.

NOx at 100 % load, corrected (ppm)

684.9628.0
8.5 %less NOx at 100 % load
Same dieselbefore and after, no changes to the engine
Independentmeasurement with a calibrated Testo 350 MCERTS
CustomerIndependent test by Optimum Power Services
CountryUnited Kingdom
SystemPerkins 2506C-E1TAG2 generator, 478 kW, day tank with Delta Xero filtration
FluidStored diesel, EN 590

The test was meant to show what the cleanliness of the diesel alone does to emissions, without modifying the engine, changing the fuel or adding chemicals. So the same thing was done twice: same generator, same stored diesel, same sampling point in the exhaust and same test plan at full load.

Optimum Power Services, an independent UK generator service company, tested a 478 kW Perkins 2506C-E1TAG2 on 1 September 2021 with stored EN 590 diesel. Delta Xero filtration then ran in the generator’s day tank, and the test was repeated on 6 September.

The exhaust was measured with a calibrated Testo 350 MCERTS analyser for 600 seconds and corrected to dry gas at 15 % oxygen. NOx fell from 684.9 to 628.0 ppm at 100 % load, an improvement of about 8.5 %. The technicians also saw visibly less smoke at start-up and in operation.

For sites with environmental requirements or ESG reporting, this is a documented figure that can be used directly. The result applies to this generator and this diesel and is not a guarantee for every installation.

The figures before and after

MeasurementBeforeAfter
NOx at 100 % load, corrected (ppm)684.9628.0
Smoke at start-up and in operationvisiblevisibly less