Wall-mounted Delta Xero unit
Emergency power

DX1001-T-PT: 95.45 % fewer particles in the diesel in a single pass

How much does the diesel unit remove in a single pass? With one particle counter before and one after the filter, particles above 4 µm were measured. They fell from 1,106,869 to 49,961 per 100 ml, 95.45 %. After two minutes the diesel left the filter at cleanliness code 9/8/6.

ISO 4406 at start (before and after the filter)

21/19/1716/15/15
95.45 %fewer particles above 4 µm in a single pass
9/8/6cleanliness code of the diesel leaving the filter after 2 minutes
18/16/13is the usual requirement for diesel, met in a single pass
CustomerIn-house test
CountryUnited Kingdom
SystemDX1001-T-PT with online particle counters before and after the filter
FluidDiesel

The test was meant to show how effectively a DX1001-T-PT unit cleans diesel in a single pass through the cartridge. Two online particle counters were fitted to the unit, one before and one after the filter, and read several times over a couple of minutes on 5 September 2022.

At the start the diesel went in at cleanliness code ISO 21/19/17 and came out at 16/15/15. After one minute the figures were 18/16/13 in and 11/10/8 out, and after two minutes 16/14/13 in and 9/8/6 out. At 4 µm, particles fell from 1,106,869 to 49,961 per 100 ml, a reduction of 95.45 % in a single pass.

Diesel from an ordinary tank can start at around cleanliness code 23 for the smallest particles. Reaching ISO 17 to 18 requires removing about 92 to 94 % of the particles. The test shows the unit achieves this in a single pass. In a standby power tank the unit runs continuously in a kidney loop, so the diesel passes the cartridge many times.

This is an in-house test on a test rig, not a measurement at a customer site.

The figures before and after

MeasurementBeforeAfter
ISO 4406 at start (before and after the filter)21/19/1716/15/15
ISO 4406 after 1 minute (before and after the filter)18/16/1311/10/8
ISO 4406 after 2 minutes (before and after the filter)16/14/139/8/6
Particles above 4 µm per 100 ml1,106,86949,961